A Importância da seletividade em proteção de redes de distribuição: estudo de caso no alimentador MAR03 da subestação 13,8 kV Maricá/RJ

Registro completo de metadados
MetadadosDescriçãoIdioma
Autor(es): dc.contributorLopes, Yona-
Autor(es): dc.contributorLeite, Matheus Felipe Ayello-
Autor(es): dc.contributorFortes, Marcio Zamboti-
Autor(es): dc.contributorTerrola e Lopes, Thales-
Autor(es): dc.creatorFigueiredo, Lucas-
Data de aceite: dc.date.accessioned2025-01-03T11:42:01Z-
Data de disponibilização: dc.date.available2025-01-03T11:42:01Z-
Data de envio: dc.date.issued2024-07-25-
Data de envio: dc.date.issued2024-07-25-
Fonte completa do material: dc.identifierhttps://app.uff.br/riuff/handle/1/33639-
Fonte: dc.identifier.urihttp://educapes.capes.gov.br/handle/capes/920093-
Descrição: dc.descriptionA proteção de sistemas elétricos de potência é uma importante área que assegura a estabilidade e integridade das redes de distribuição elétrica, envolvendo uma série de estratégias e tecnologias projetadas para prevenir falhas, minimizar o impacto de interrupções e manter a continuidade do fornecimento de energia. Um dos principais desafios é assegurar a coordenação eficiente entre os dispositivos de proteção em diversos níveis do sistema, visando isolar seletivamente apenas a seção comprometida durante uma falta, evitando interrupções desnecessárias em segmentos operacionais não afetados. A complexidade aumenta com a necessidade de ajustar esses dispositivos para responder adequadamente a uma variedade de condições de faltas, o que requer um equilíbrio preciso entre sensibilidade e seletividade. Um estudo de caso sobre a aplicação da proteção de sobrecorrente será desenvolvido neste trabalho, focando no sistema elétrico de um alimentador de 60 km de extensão localizado na cidade de Maricá, no estado do Rio de Janeiro. Ele conta com um IED na cabeceira do circuito, com três religadores de rede e diversos elos fusíveis. Para o estudo, é feito um levantamento detalhado das características ao longo da rede, incluindo equipamentos de proteção, tipos de condutores e níveis de curto-circuito. Com isso, são definidos os ajustes de proteção necessários para garantir a seletividade considerando os limites de ampacidade dos condutores. Uma bancada de testes com um relé SEL 451-2 e uma mala de testes Omicron CMC 356 é montada para avaliar os ajustes parametrizados e seu desempenho para curto-circuitos trifásicos, bifásicos e monofásicos com impedância de aterramento. Os resultados demonstram a correta atuação dos equipamentos de proteção e como a precisa seletividade maximiza o fornecimento de energia em situações de falta na rede-
Descrição: dc.descriptionThe protection of electrical power systems is a important area that ensures the stability and integrity of electrical distribution networks, involving a series of strategies and technologies designed to prevent failures, minimize the impact of interruptions and maintain continuity of energy supply. One of the main challenges is to ensure efficient coordination between protection devices at different levels of the system, aiming to selectively isolate only the compromised section during a fault, avoiding unnecessary interruptions in unaffected operational segments. Complexity increases with the need to tune these devices to appropriately respond to a variety of fault conditions, which requires a precise balance between sensitivity and selectivity. A case study on the application of overcurrent protection will be developed in this work, focusing on the electrical system of a 60 km long feeder located in the city of Maricá, in the state of Rio de Janeiro. It has an IED at the head of the circuit, with three network reclosers and several fuse links. For the study, a detailed survey of the characteristics throughout the network is carried out, including protective equipment, types of conductors and short circuit levels. With this, the necessary protection adjustments for the short values in the network are defined based on the coordination, selectivity and ampacity limits of the cables. A test bench with an SEL 451-2 relay and an Omicron CMC 356 test case is assembled to evaluate the parameterized settings and their performance for three-phase, two-phase and single-phase short circuits with grounding impedance. The results demonstrate the correct performance of the protection equipment and how precise selectivity maximizes energy supply in situations of network fault-
Descrição: dc.description75 f.-
Formato: dc.formatapplication/pdf-
Idioma: dc.languagept_BR-
Direitos: dc.rightsOpen Access-
Direitos: dc.rightsCC-BY-SA-
Palavras-chave: dc.subjectProteção de redes de distribuição-
Palavras-chave: dc.subjectProteção de sobrecorrente-
Palavras-chave: dc.subjectSeletividade-
Palavras-chave: dc.subjectIED-
Palavras-chave: dc.subjectSistema de distribuição de energia-
Palavras-chave: dc.subjectProteção de sistema elétrico-
Palavras-chave: dc.subjectMaricá (RJ)-
Palavras-chave: dc.subjectProtection of distribution networks-
Palavras-chave: dc.subjectOvercurrent protection-
Palavras-chave: dc.subjectSelectivity-
Palavras-chave: dc.subjectIED-
Título: dc.titleA Importância da seletividade em proteção de redes de distribuição: estudo de caso no alimentador MAR03 da subestação 13,8 kV Maricá/RJ-
Tipo de arquivo: dc.typeTrabalho de conclusão de curso-