Método para obtenção de sensibilidade e seletividade da proteção contra faltas monofásica-terra em sistemas aterrados por alta impedância

Registro completo de metadados
MetadadosDescriçãoIdioma
Autor(es): dc.contributorBorges, Thiago Trezza-
Autor(es): dc.contributorMonteiro, Paulo Roberto Duailibe-
Autor(es): dc.contributorOliveira, Carlos Henriques Ventura do Rosário-
Autor(es): dc.creatorPereira, Matheus Mendanha-
Data de aceite: dc.date.accessioned2024-07-11T18:31:31Z-
Data de disponibilização: dc.date.available2024-07-11T18:31:31Z-
Data de envio: dc.date.issued2021-09-13-
Data de envio: dc.date.issued2021-09-13-
Data de envio: dc.date.issued2020-
Fonte completa do material: dc.identifierhttps://app.uff.br/riuff/handle/1/23189-
Fonte: dc.identifier.urihttp://educapes.capes.gov.br/handle/capes/772209-
Descrição: dc.descriptionA utilização do aterramento de sistemas por alta impedância é um método amplamente aplicado dentre os sistemas industriais com tensão entre 2,4 e 13,8 kV, devido às correntes de falta monofásica para a terra tipicamente inferiores à 10 amperes. Apesar de nesta configuração o sistema possuir baixas correntes durante faltas monofásica-terra, a filosofia de proteção implementada normalmente atua mediante a medições de tensão de sequência zero durante estas situações de anormalidade, garantindo confiabilidade na atuação no entanto comprometendo a seletividade do processo. Com o intuito de amenizar as características negativas citadas dos sistemas aterrados por alta impedância, este trabalho apresenta uma proposta de esquema de proteção contra faltas monofásicas através de um estudo de caso, no qual foi utilizada como referência uma usina hidroelétrica real aterrada por alta impedância, servindo como base de estudo. O esquema propõe a utilização de TCs do tipo Ground Sensor de baixa relação em conjunto com unidades de proteção de sobrecorrente de neutro coordenadas com proteções de sobretensão de neutro já implementadas, considerando as metodologias de atuação da proteção por seletividade cronológica e seletividade lógica. Neste trabalho, a análise acerca do funcionamento do método proposto foi feita através de modelagens e simulações utilizando a ferramenta Simulink®, apresentando resultados coerentes e satisfatórios considerando o mínimo esperado de confiabilidade, sensibilidade, seletividade e rapidez de uma filosofia de proteção para um sistema elétrico de potência.-
Descrição: dc.descriptionThe use of high impedance grounding systems is a method widely applied among industrial systems with voltage between 2.4 and 13.8 kV, due to the single-phase earth fault currents typically below 10 amps. Although in this configuration the system has low currents during single-phase-to-ground faults, the implemented protection philosophy usually operates by measuring zero sequence voltages during these abnormal situations, guaranteeing reliability in its performance, however compromising the process selectivity. In order to reduce the negative characteristics mentioned of high impedance grounded systems, this work presents a proposal for a protection scheme against single phase faults through a case study, in which a real hydroelectric plant grounded by high impedance was used as a reference, serving as a study base. The scheme proposes the use of a low current ratio Ground Sensor CTs in conjunction with neutral overcurrent protection units coordinated with neutral overvoltage protections already implemented, considering the methodologies of the protection by chronological selectivity and logical selectivity. In this work, the analysis about the operation of the proposed method was done through modeling and simulations using Simulink®, presenting coherent and satisfactory results considering the minimum expected reliability, sensitivity, selectivity and speed of a protection philosophy for an electrical power system.-
Formato: dc.formatapplication/pdf-
Idioma: dc.languagept_BR-
Direitos: dc.rightsOpen Access-
Direitos: dc.rightsCC-BY-SA-
Palavras-chave: dc.subjectLocalização de faltas-
Palavras-chave: dc.subjectProteção de sistemas elétricos-
Palavras-chave: dc.subjectAterramento de alta impedância-
Palavras-chave: dc.subjectRelés de proteção-
Palavras-chave: dc.subjectSeletividade lógica-
Palavras-chave: dc.subjectSeletividade da proteção-
Palavras-chave: dc.subjectProteção de sistema elétrico-
Palavras-chave: dc.subjectAterramento elétrico-
Palavras-chave: dc.subjectEngenharia elétrica-
Palavras-chave: dc.subjectRelé de proteção-
Palavras-chave: dc.subjectSoftware-
Palavras-chave: dc.subjectCódigo aberto (Computação)-
Palavras-chave: dc.subjectFault location-
Palavras-chave: dc.subjectPower system protection-
Palavras-chave: dc.subjectHigh-resistance grounding-
Palavras-chave: dc.subjectProtection relay-
Palavras-chave: dc.subjectLogic selectivity-
Palavras-chave: dc.subjectProtection selectivity-
Título: dc.titleMétodo para obtenção de sensibilidade e seletividade da proteção contra faltas monofásica-terra em sistemas aterrados por alta impedância-
Tipo de arquivo: dc.typeTrabalho de conclusão de curso-
Aparece nas coleções:Repositório Institucional da Universidade Federal Fluminense - RiUFF